(1) It can reduce the impact on the power grid and reduce the capacity of the transformer.

When the ordinary squirrel cage motor is directly started at no load and full pressure, the starting current will reach 5 to 7 times of the rated current. When the motor capacity is relatively large, the starting current will cause the grid voltage to drop sharply, which will destroy the normal operation of other equipment in the same grid, and even cause the grid to lose stability and cause more accidents. Therefore, it is generally required that the voltage fluctuation caused by the motor that is frequently started is not more than 10%; the voltage fluctuation caused by the motor that is occasionally started is not more than 15%. After the soft start, the starting current can be reduced to 1.5 to 3 times of the rated current, which can greatly reduce the fluctuation rate of the grid voltage.

For motors powered by separate transformers. When direct full-pressure starting is used, the capacity of the motor is required to be no more than 80% of the transformer capacity. When using a soft start, the capacity of the transformer can be the same as the apparent power of the motor (typically S = 1.1 PN).

The equivalent circuit of the transformer--motor unit is shown in Figure 1. U0 is an infinite grid. U1 is the motor terminal voltage. XT is the short-circuit impedance of the transformer, when rated, when the motor current is equal to the rated current of the transformer. The voltage drop across the XT is the short circuit voltage value UK of the transformer. If the motor has a maximum current of 3IN during soft start. Then the pressure drop across the XT is 3UK. UK=(4~10.5)%UN for small and medium-sized power transformers, UK=(12.5~17.5)%UN for large transformers. In general, as long as the motor starts, the terminal voltage is not lower than 65% of the rated voltage ( The maximum current can be started successfully.

For rated operation, I=IN, U0-U1=UK, U1=UN. If calculated according to the limit: UK = 17.5%; I = 3IN. Then: U1=U0-3UK=UN-2×17.5% UN=65%UN. It can also meet the starting requirements. Other situations will be U1>65%. Not a problem.

For the case of motor and other load sharing transformers, it is generally required that the capacity of the motor that is frequently started is not more than 20% of the capacity of the transformer; the capacity of the motor that is occasionally started is not more than 30% of the capacity of the transformer.

If Imax=6IN when the full pressure is started and Imax=3IN when the soft start is started, the motor capacity of the frequently started motor can reach 40% of the transformer capacity from the viewpoint of the line voltage drop such as the equal current; the motor capacity that occasionally starts can reach the transformer. 60% of capacity.

(2) can reduce the damage to the motor and extend the life of the motor

1. The large current when the motor is directly pressed at full pressure produces a large impact force on the stator coil and the rotor squirrel of the motor, which increases the wear of the stator coil (especially the end) and the iron core, and destroys the winding insulation; The impact force on the squirrel cage is also prone to breakage, causing motor failure. The magnitude of the electric power is proportional to the square of the current. The electric power at the direct full-pressure start is 36 times that of the normal rated operation (according to Imax=6IN). The electric power at the soft start is 9 times that of the normal rated operation. The visible effect is very obvious.

2. The large current when the motor is directly started at full pressure causes a large amount of Joule heat to be generated in the stator winding. Burns the winding insulation and reduces the life of the motor. Soft start can greatly reduce heat generation. Improve motor life. High heat is generated at the maximum current. Joule heat is proportional to the square of the current, so the concentrated high heat is reduced by a factor of two. Generally, the soft start is no-load or light-load start, and the maximum current is usually around 2IN. At this time, the high heat is only straight. Undoubtedly, it has great benefits for extending the life of the motor.

3. When the motor is directly started at full voltage, the rated voltage is instantaneously applied to the motor windings. At this time, the operating overvoltage is generated. In the most unfavorable case, the overvoltage will reach 5 times of the rated voltage, which will cause great damage to the motor insulation. Many motor damages occur when the switch is turned on due to the operating overvoltage.

(3) can reduce mechanical damage and extend mechanical life

The maximum torque of the motor when starting directly at full pressure is about twice the rated torque. For gear transmission equipment, a large impact force will accelerate or even break the gear; for belt transmission equipment, the belt is enlarged. The wear and tear even breaks the belt; for the pump type equipment, it will produce a "water hammer effect" to damage the pipe and the impeller. During soft start, the motor accelerates slowly and the torque is gradually increased, completely eliminating the above hazards. The motor speed rises slowly during soft start, which is beneficial to the full placement of lubricating grease and eliminates the phenomenon of dry grinding. These greatly reduce the damage to the motor and help to improve the life of the mechanical equipment.