Low-voltage three-phase asynchronous motor energy efficiency rating and test procedure

Low-voltage three-phase asynchronous motor energy efficiency rating and test procedure

Motor energy efficiency evaluation mainly refers to or quotes GB/T1032 three-phase asynchronous motor test method, then which method is used for low-voltage three-phase asynchronous motor energy efficiency test? And what are the method steps?

First, the energy efficiency test mainly has the following standard methods:

(1): Method A - Input-Output Method

(2): Method B - loss analysis and input-output method for indirect measurement of stray loss

(3): C method - loss analysis and feedback method Introduction to measuring stray loss

(4): E method - loss analysis and direct method to measure load stray loss

(5): E1 method - loss analysis and recommended load stray loss

(6): F method - equivalent circuit and direct method to measure load stray loss

(7): F1 method - equivalent circuit and recommended load stray loss

(8): G method - reducing voltage load method and direct method to measure load stray loss

(9): G1 method - reduce voltage load method and recommended load stray loss

(10): H method - circle chart method

Second, low-voltage three-phase asynchronous motor energy efficiency test method - B method:

GB/T18613 small and medium-sized three-phase asynchronous motor energy efficiency limit value and energy efficiency rating for motor energy efficiency test reference G / BT1032 three-phase asynchronous motor test method B method - measuring input power and output power loss analysis method.

Third, the test B method steps:

(1): Determine if the power supply meets the requirements

(2): Determine the accuracy of the meter range meets the requirements

(3): Motor inspection, nameplate data check; wiring diagram, wiring method check, etc.

(4): Determination of cold DC resistance

(5): Thermal test

(6): Load test

(7): No-load test