Mar 12, 2019 Leave a message

How to determine the performance level of the motor qualitatively by the no-load current of the motor?

How to determine the performance level of the motor qualitatively by the no-load current of the motor?

Generally speaking, the no-load current of the motor can roughly reflect the performance of the motor. In all aspects of motor production, testing, sales and use, the no-load current of the motor can be used as a qualitative judgment standard for the motor state. Today, Ms. participated in the no-load current of the motor and screamed at everyone.

No-load, load current and power data relationship

There is an intrinsic relationship between the rated voltage, rated current and no-load current data. Once the value is beyond the normal, you should be alert to the failure of the motor.

What is no-load current?

When the output shaft of the three-phase asynchronous motor has no load or the torque is zero, it is no-load operation. At this time, the current in the three-phase winding of the stator is mainly the excitation current, which is usually called the no-load current. Most of the excitation current, which accounts for the no-load current, is used to generate the rotating magnetic field, which is the reactive component of the no-load current. The small proportion is corresponding to the no-load iron consumption, no-load mechanical consumption, wind wear, and stray consumption. The active component is negligible in qualitative analysis. Therefore, the no-load current can be considered as a reactive current.

No-load current and motor performance

Based on the above point of view, the smaller the no-load current, the better, so that the power factor of the motor is increased, and it is beneficial to supply power to the grid. If the no-load current is large, because the wire carrying area of the stator winding is constant, and the current allowed to pass is constant, the active current flowing through the wire can only be reduced, and the load that the motor can drive is reduced. The motor output is reduced, and the winding is prone to heat when the load is too large.

The no-load current should not be too small. If the design is too small, the starting torque may be exceeded and the maximum torque may fail.

No-load current and rated current

Generally, the no-load current of a small motor is about 30% to 70% of the rated current, and the no-load current of the large and medium-sized motor is about 20% to 40% of the rated current. The no-load current specific to a motor is generally not marked on the nameplate or product manual of the motor.

3

The load current is the value of the stator current actually detected when the motor is dragging the load. This value varies with the load.

Current calculation example

A 55kW motor should have a rated current of less than 110A. The no-load current of the motor is related to the quality of the motor. Generally, the no-load current of a 55 kW motor is about 0.3 to 0.4 times the rated current, that is, about 33 to 44 A.